- NEW YORK
- [ 2007 Residential Code of New
York State ]
E3503.1 Grounded and ungrounded service conductor size. Conductors used as ungrounded service entrance conductors, service lateral conductors, and feeder conductors that serve as the main power feeder to a dwelling unit shall be those listed in Table E3503.1. The main power feeder shall be the feeder(s) between the main disconnect and the lighting and appliance branch-circuit panelboard(s). Ungrounded service conductors shall have a minimum size in accordance with Table E3503.1. The grounded conductor ampacity shall be not less than the maximum unbalance of the load and its size shall not be smaller than the required minimum grounding electrode conductor size specified in Table E3503.1.
TABLE E3503.1 SERVICE CONDUCTOR AND GROUNDING ELECTRODE CONDUCTOR SIZING
CONDUCTOR TYPES AND SIZES—THHW, THW, THWN, USE, XHHW
(Parallel sets of 1/0 and larger conductors are
permitted in either a single raceway or in separate raceways)ALLOWABLE
AMPACITYMINIMUM GROUNDING
ELECTRODE CONDUCTOR SIZEaCopper
(AWG)Aluminum and copper-clad aluminum
(AWG)Maximum load
(amps)Copper
(AWG)Aluminum
(AWG)4 2 100 8b 6c 3 1 110 8b 6c 2 1/0 125 8b 6c 1 2/0 150 6c 4 1/0 3/0 175 6c 4 2/0 4/0 or
two sets of 1/0200 4d 2d 3/0 250 kcmil or
two sets of 2/0225 4d 2d 4/0 or
two sets of 1/0300 kcmil or
two sets of 3/0250 2d 1/0d 250 kcmil
or two sets of 2/0350 kcmil or
two sets of 4/0300 2d 1/0d 350 kcmil
or two sets of 3/0500 kcmil or
two sets of 250 kcmil350 2d 1/0d 400 kcmil
or two sets of 4/0600 kcmil or
two sets of 300 kcmil400 1/0d 3/0d
For SI: 1 inch = 25.4 mm.
a. Where protected by a metal raceway, grounding electrode conductors shall be electrically bonded to the metal raceway at both ends.
b. Eight AWG grounding electrode conductors shall be protected with metal conduit or nonmetallic conduit.
c. Where not protected, 6 AWG grounding electrode conductors shall closely follow a structural surface for physical protection. The supports shall be
spaced not more than 24 inches on center and shall be within 12 inches of any enclosure or termination.
d. Where the sole grounding electrode system is a ground rod or pipe as covered in Section E3508.2, the grounding electrode conductor shall not be
required to be larger than 6 AWG copper or 4 AWG aluminum. Where the sole grounding electrode system is the footing steel as covered in Section
E3508.1.2, the grounding electrode conductor shall not be required to be larger than 4 AWG copper conductor.
- [ 2007 Residential Code of New
York State ]